andrew smith asked ... 2009 fiesta 1388 cc titainum?    |    Eric asked ... Strimmer fuel line?    |    Frank asked ... Working fine. No cold air?    |    c.m.brown asked ... Replace chuck on aeg power drill sb2e 700r?    |    tom dimmock asked ... How can i mend the lid on russell hobbs elec?    |    Click here to ask your question

Vaillant turbomax VUW/GB282/1E heating fault?

I was called to take a look at this particular model earlier today and whilst waiting for a response from Vaillant thought I may test the local knowledge. We have a situation where the bolier will fire perfectly satisfactorarily for heating and hot water and switch between the two without fault, however once back in heating mode the moment the timeclock is turned off or room stat. or boiler heating temperature thermostat is turned down the boiler fails to relight when there is next a demand for heating. The hot water still operates but then after the boiler returns to demand for heating light on but no further start up sequence. Any ideas other than a suspect P.C.B or is that a cop out attempt at a cure ?
Mark Cryer, November 2007
if it has a built in time clock this could be the problem, try unplugging the clock from the pcb so demand is from roomstat only and not via timeclock. hope that helps

tojo, November 2007