dave s asked ... Transmission not working?    |    Tom asked ... Replace rear right door upper right latch cable - high roof?    |    ian asked ... Vaillant timeswitch 150 analogue unit (clock stopped?    |    Art Cour asked ... How do I get engine cowling off to find gas leaking?    |    liz asked ... Changing a belt?    |    Click here to ask your question

how do i bleed the header tank?

i have a baxi solo and im having problems getting it started,the pump is grinding and it is tripping the overheat switch,i have been advised to bleed the whole system including the header tank?is this the small read filling/expansion tank below,and are there any more points other than the pump and radiators i should bleed
r, September 2005
need to no if its a sealed system heating system or open vented . if its sealed the red expansion vessel is there to accomodate the pressure increase when the water heats up , is there enough water in the system ?,some boilers have a auto air valve ensure this is opened by turning or loosening the black cap on top .at the hot water cylinder you should have an air point at the coil thats where the flow and return from the heating system enters the cylinder open it and u should get air . to me sounds like u have a sealed heating system so ure prob going to have to fill it up using the filling loop normal pressure is 1.5 bar there should b a gauge on the red expansion vessel .

fitter, September 2005