58 mins ago Karen asked ... Royal 480nt cash register?    |    andrew smith asked ... 2009 fiesta 1388 cc titainum?    |    Eric asked ... Strimmer fuel line?    |    Frank asked ... Working fine. No cold air?    |    c.m.brown asked ... Replace chuck on aeg power drill sb2e 700r?    |    Click here to ask your question

What is causing my Ariston boiler microsystem 21RFF1 to gain pressure ?

What is causing my Ariston boiler microsystem 21RFF1 to gain pressure causing the safety valve to open and shuts the boiler down - not due to overheating.
John Shailer, November 2008
I have changed the expansion vessel and it is now working perfectly

John, November 2008
There are several things that can cause this problem, does the pressure increase when the boiler is not in use? if so maybe the filling loop is letting by or your water to water heat exchanger has failed, try disconnecting the filling loop and check if the pressure still increases. If the problem is when the boiler is running then it could be your expansion vessel has failed or just needs to be re-pressurised (with air).

Martin, November 2008