GG asked ... Fix food processor motor?    |    T asked ... How do I turn the delay off on Electrolux DX302 dishwasher?    |    Helen asked ... How can I mend my Kenwood Gourmet FP505?    |    Roy Turner asked ... Kohlangaz Gosford HE fire?    |    Peter asked ... How can I mend a Powerwasher PRO PRO1800PWE?    |    Click here to ask your question

what is the normal operating pressure for vokera linea 24?

the pressure is set cold at between one and one and a half,
when heating is on pressure rises slightly as it should, however when switched off overnight the pressure rises to about two and a half, bleeding the radiator reduces the pressure again.
A Griff, December 2008
For the pressure to rise overnight either air or water is being added to the system somehow. Is your filling loop a permanent connection? If it is I would suspect that the valve in the loop is 'leaking' mains pressure into your heating system. You could perhaps verify this by turning your stopcock completely off at bed time (ie eliminating mains pressure from the equation). If in the morning your system pressure is correct then you have a faulty valve. I can't think what else it could be!

Richard, December 2008
link Click here to see other fixes for Vokera.