narnia asked ... Matsui ct-111ss?    |    Jason asked ... How to fix handset problems ( intercom ) and access control?    |    andy asked ... Samsung VP-D60 camcorder?    |    Shopper asked ... Poor Renault Radio Reception?    |    reg bardle asked ... Lg 7kg dd?    |    Click here to ask your question

I have an ideal response 120 combi boiler with anoisy fan?

I have a noisy fan, do I need to replace the fan assembly or just the fan itself as they are listed separately as available parts. Is this something a competent DIYer can cope with?
Philip Leeds, February 2009
order the fan ass and when it is changed carefully check inside the heat exchanger for any leaks(common fault on poor boiler)fan is easy to change but should be done buy a engineer and a performance test/gas rate or burner pressure done after reassembling.if it was my boiler i would change spark electrodes at the same time as these are the main cause of noisy ignition(booming)when lighting

jim, February 2009