Steve asked ... Gilera runner 180 vxr 2001 ignition replacement?    |    Janboy68 asked ... How can I mend my KitchenAid Artisan toaster?    |    rick asked ... How can I fix my portable Zenith DVP615 DVD player? When I p?    |    Jim asked ... How can I get my scarifier to work?    |    george crawford asked ... Citroen C3 Picasso?    |    Click here to ask your question

Worcester 19/24 cbi boiler?

hello i have a Worcester 19/24 cbi boiler it was working perfect till the other day but now it runs for about 3-5 mins then shuts down for about 3 mins then you can hear the fan and it firers up again,and so it carries on with the same cycle,it does not lock out .when it shuts down the orange light on the far left is on continuous then when it is running the far left light and the middle light stay on continuous,any help would be appreciated,thanks stuart
Stuart, March 2009
Hmmm one of these
Clean,polish the sense and ignition electrodes and wipe ignition leads,

justeve, March 2009
PCB fault for sure.

Not much else to go wrong on these

griffiths heating, March 2009
link Click here to see other fixes for Worcester.