Pam asked ... Do I need to open the housing to dry the motor?    |    James asked ... Remove enterprise enrolment from an Asus Chromebook C523N?    |    tom schwartz asked ... Bosch maxx 6?    |    Noman asked ... Reverse light switch?    |    Suzie asked ... Stuck Feed dog?    |    Click here to ask your question

diy plumbing?

my sime boiler heats the rads fine but latley i find that the hotwater only gets warm. the boiler fires up ok. to get hot water u need to have the central heating on for a while. without the central heating on it only gets warm
iain, March 2009
maybe its the diverter valve or diaphram

T.T., March 2009
Could be a number of reasons. Firstly have you checked the thermostat on the hot water cylinder, probably ok but worth checking. Then it could be the valves (3 way valve on a Y plan or one of the 2 way valves on a S plan). With the water on and heating on check that they are closed for heating and open for the hot water. You will find a lever on the side of most to indicate and allow for manual operation of them. Other factors would be the boiler stat as if set too low the hot water can return too quickly the boiler will close down. Same if pump set too high. Could also be a fault in the boiler PCB, wiring or controls as well.
If you've done the first checks below you may have to get an Engineer to look at it.

Stephen, March 2009