2 hours ago Janboy68 asked ... How can I mend my KitchenAid Artisan toaster?    |    rick asked ... How can I fix my portable Zenith DVP615 DVD player? When I p?    |    Jim asked ... How can I get my scarifier to work?    |    george crawford asked ... Citroen C3 Picasso?    |    Maggie asked ... How can i mend my kettle?    |    Click here to ask your question

external lights and sockets?

if i make sure that all external sockets/lighting go via an rcd does this conform to the 17th edition regs(part P)?
andy b, May 2009
It would if you are part p registered and complete a minor works certificate. Also the work itself has to comply to regs ( correct cable used and so on ).

If you wire a new circuit for this then you would need to test the full circuit and also the incoming zs and ze.

Roberts & Son Electrical, June 2009
The 17th Edition does require circuits to be rcd protected, but there are other factors that need to be taken into consideration for them to comply.

Part P is a system whereby non electrically skilled people (plumbers, ceiling fitters, brickies etc) can certify electrical work without having to first notify building control.

Adam, May 2009