Lou asked ... Mac Allister 35cm electric lawn mower?    |    Ronald Charlwood asked ... Beko fridge/freezer not cold enough?    |    John Broadbent asked ... Advise?    |    suzy asked ... Brother kh-940 not in sync with DAK9 in interactive knitting?    |    Susan asked ... How can I stop my steam iron spraying water with the steam?    |    Click here to ask your question

Ferrpli F30 over pressure?

My Ferroli F30 works well except when the heating is on the pressure in the system goes over 3.5 bar and the P.R.V dumps the excess as it is supposed to do. The starting pressure is 1 bar. I understand from the manuel the normal running pressure is 1.5 to 2 bar. When the system has cooled down the pressure is 1/2 a bar. All the rads are getting hot. Any help would be appreciated.
Jeff Bridgend, May 2009
Problem solved,
The Shrader valve on the expansion vessel had failed.
All the air pressure had been lost. I replaced the valve and repressurised the tank. It all works perfectly now. Tulas you were not far off the mark.
Thanks

Jeff Bridgend, May 2009
expansion vessel goosed or pipework 2 it is blocked

tulsa mclean, May 2009