Bob asked ... Charger fault?    |    Terry nelson asked ... How to remove the flexible shaft from a curved shaft ryobi t?    |    Matt Longmore asked ... Non-start on Flymo XLT 250?    |    John asked ... How to fix my fireplace?    |    Ian Scott asked ... Remove cover off gas boiler?    |    Click here to ask your question

Vaillant vcw sine T3W pressure drop?

Hi

I have a vaillant vcw sine t3w boiler which is fine on the water circuit, but when central heating side cuts in the pressure increases to around 3+ bar but then after boiler cuts out the pressure drops to which point it overheats and then wont fire up again. I am keeping my eye on it and will have to top it up daily during winter to stop it from cutting out. During the summer when central heating is not used it is fine and doesnt lose pressure. Any suggestions on possible causes/fixes would be appreciated.
james, September 2009
the expansion vessel is probably flat and needs re-pressurised, easy job for a qualified engineer. it may be burst or the pipe leading to it may be blocked, but that's far less common.

Ian, September 2009