59 mins ago Melodie asked ... How do I remove and change the basket? Duratech Identity Gu?    |    Kathy asked ... Samsung ER-4915?    |    Mark asked ... Oven door removal?    |    Jt asked ... Where to buy mt270x petrol cap?    |    Jo asked ... How to engage clutch on old sewing machine to engage needle?    |    Click here to ask your question

Can I pressurise system myself?

Hello, I have an Ariston Genus boiler downstairs, a hot water cylinder upstairs and in the roof a white Velum pressure vessel, teed off a 15mm with a release valve at the top of that.Next to that is another 15mm with another release valve.The guage on the boiler never gets above the second notch in the red '0' section and the radiators struggle to get warm most of the time. The boiler can be very noisy sometimes (like a squeeling Pig), usually on start-up. Any ideas please?
Michael Coombe, November 2009
Thanks, I looked for a fill-loop already but this system doesn't seem to have one.

Mike, November 2009
under the boiler there should be a filling loop.open both valves until pressur on gauge reeds about 1.2 bar

albob, November 2009