Morne asked ... My defy dtl 125 toploader?    |    Ernie asked ... How to fix gearchange ldv maxus van 2006?    |    Cuckoo asked ... Changing batteries on a fixed bt corded phone?    |    Marc Nollid asked ... Nissan Micra mk 5 2018 rear seat mecanism?    |    Maggie asked ... New Home 535?    |    Click here to ask your question

boiler problem?

valliant boiler my sons boiler pressure keeps dropping the over flow pipe from boiler which goes out side is dripping. water turbo max the model
kevin lilley, December 2009
it may be few things, are you sure you have turned the filling loop off.

It may be the PRV pressure relief valve is faulty, as it is not closing and letting water through.

Expansion vessel may need charging, but this can be checked out by just draining the bolier only, and then checking with the pressure guage like a cycle pump and see if you get reading between 0.75-1bar.

siraz, December 2009