What is wrong with the pressure?

Hello

I have a Vokera Linea 24, for the past few months the pressure has been going up to nearly 4 each day.

Have to bleed the radiators morning and night to place back to 1.5.

I turn the water off through the day so the pressure stays the same till I get in.

We have had a part replaced which only cost £20 but that hasn't done anything.

Any help or advice would be much appreciated.

Thanks

Sam
Samantha, June 2010
filling loop is passing or plate heat exchanger is burst. only way to test is by disconnecting filling loop pipe. if water is coming out even with it turned off then there's your problem. if pressure still rises with it disconnected but no water from pipe then plate heat exchanger needs replaced.

Ian, June 2010