GG asked ... Fix food processor motor?    |    T asked ... How do I turn the delay off on Electrolux DX302 dishwasher?    |    Helen asked ... How can I mend my Kenwood Gourmet FP505?    |    Roy Turner asked ... Kohlangaz Gosford HE fire?    |    Peter asked ... How can I mend a Powerwasher PRO PRO1800PWE?    |    Click here to ask your question

Fluctuating D.H.W temperature.Ferroli Modena 102?

The D.H.W from my Ferroli Modena 102 fluctuates from hot to cold whilst filling the bath or taking a shower (mixer tap shower) and also at basins.The burner comes on for approx 15 seconds then switches off,firing up again approx 10 seconds later in a continuous cycle.All other operations seem to be fine.I have replaced the D.H.W flow temperature sensor but this has had no effect.Are there any further checks I can make before having to call out a proffessional?
Rupert, December 2006
flow senscor switch

gasman pete, November 2011
my pilot light keeps going out when i switch my heating on boiler make ferroli model modena 102

catherine, December 2010
The central heating goes on standby but does not actually come in on the Ferroli Modena 102. The water heating system is okay.

Rebecca Nisbet, December 2010
is the red tube at the bottom or top

DAVE, May 2010
Can anyone confirm the part number for the venturi for the Modena 102 ?

Thanks

Martin P, February 2010
please can you tell me am corgi fitter & acops aproved i have finished work know & its is for my sister,s the boiler is & foroli modena 102 the problem is it is going above 3 barr & going out of the discharge overflow pipe out side found two leaks on boiler & repaird them can you tell me is this the pressor vesale that is the ploblem love liz

liz hollyoke, February 2010
Had the same problem as Les. took off fan housing.( 2 screws , then tilt up ,so it unhooks at the back) the red part of venturi was smashed to pieces inside. replaced that (£6) and fingers crossed all ok now !!

paul, January 2010
is changing the venturi a job for the experts ? or competent diy ??
thanks

Paul, January 2010
its probably the venturi tube situated inside the fan casing replace with kit about £10.00.

workshy, December 2009
hi phil tried that m8 i tried with cover and hey presto no flutuation but when i put cover back on same prob any ideas m8
many thanks les

les, November 2009
Phil Hardaker is the man!! I've had this same problem for ages and i'm not exactly Mr. DIY so i asked my father in law, he thought it may be a sensor. I'd had enough so i followed Phils instructions and it's working perfectly again, cheers Phil

Martin Allison, November 2009
Phil, you are a star. I had the same problem, cleaned the connector and now back to normal. Nice one.

Alan Stokes, October 2009
I had this problem,the burner coming on when running a hot bath,shower or just hot water to do the washing up,the burner kept going off then coming back on every 15 seconds or so,so i followed the advice of Phil Hardaker and removed yellow and green connector and blew out debris and brushed connector clean,refitted and replaced cover and it worked.
Thanks again.

Steve Collins, December 2008
it might be you have a dirty or broken venturi, which operates the air pressure switch. it is located in the fan housing and costs abut £5.

Dave Steele, December 2007
At the top of the boiler is the fan and copper coil. There are two fan electrical connectors side by side on the top front of the copper coil. Behind these is a single connector, usually green and yellow wiring. This connector can collect dust etc meaning intermittent firing.

Pull the connector off the contact and give it, and the contact, a good blow, freeing it of dust etc.

Reconnect and the problem should be solved. Remember to turn the boiler off first.

Regards

Phil

Phil Hardaker, December 2006