Andrew - C asked ... Stannah 400?    |    Liam asked ... Belts for old WEBB Mower?    |    Leith asked ... Bosch Classix Type WKM41 front loader washing machine?    |    Pam asked ... Do I need to open the housing to dry the motor?    |    James asked ... Remove enterprise enrolment from an Asus Chromebook C523N?    |    Click here to ask your question

How do you pessurise a Valiant 824e?

I have a valiant 824e combi boiler, and want to remove a radiator to decorate, how do i repressurise the boiler when I reconnect the radiator. I know on most combi boilers there is a pressurising loop but cannot sse one on this boiler.
Ken, February 2007
on the early vailant 824 the filling loop is internal and is situated under the right hand side of the boiler, there is usuly an L shaped key, if the key is not available. remove the grill under the boiler you will see a round hole in the brass fitting where the cold water goes in to the boiler, inside you will see the slot that the key will fit in. if you dont have the key use a stubby flat blade screw driver open the valve slowly and alow water in to the boiler untill the pressure is correct and then switch it off again. done

Mark, February 2007
you have an internal fill. look under boiler there is a knurled knob (blue) that is your fill

hi-spec plumbing, February 2007