Leith asked ... Bosch Classix Type WKM41 front loader washing machine?    |    Pam asked ... Do I need to open the housing to dry the motor?    |    James asked ... Remove enterprise enrolment from an Asus Chromebook C523N?    |    tom schwartz asked ... Bosch maxx 6?    |    Noman asked ... Reverse light switch?    |    Click here to ask your question

Hi my mum has a ariston combi boiler which has had to be repressurised?

twice in the space of 2 weeks. I repressurised it tonight to 1.5 bar and just two hours later the heating has stopped and its down to zero pressure already.
When i repressurised it there seemed to be a sound of running water down the overflow pipe.Any idea what is causing this?
Thanks
David Clarkson, March 2007
likely that the valve is letting bye or the expansion vessel is flat. The red valve which normally says three bar on it (connected to the overflow pipe) can be unscrewed and cleaned. When the system is running if the pressure shoots up to 3 or above the likely cause is a flat or damaged expansion vessel.

andy, March 2007
link Click here to see other fixes for Ariston.