Eric asked ... Strimmer fuel line?    |    Frank asked ... Working fine. No cold air?    |    c.m.brown asked ... Replace chuck on aeg power drill sb2e 700r?    |    tom dimmock asked ... How can i mend the lid on russell hobbs elec?    |    Jerry asked ... Alpine 7287?    |    Click here to ask your question

my arrison combi boiler runs to the max pressure?

my arrison combi boiler runs to the max pressure when its running but when i turn it off and everything cools down the pressure drops to 1 bar or less if i top it up to 2 bar (recommened by the installer) when i run the heating agian it looks like the needle will go off the pressure gauge and i find myself bleeding some water out of a radiator just to get it down can anyone point me to what the prblem is?
Gary, April 2007
The pressure should be between 1 to1.5 when the boiler is cold and nothing running. No more than this. The pressure increases in proportion to the temperature, so the higher you turn the temp control for the heating the higher the pressure will go until it reaches a max around 3. The pressure relief valve will release pressure and then close itself off(in a perfect world ).
If the pressure rises rapidly there may be a deeper problem but just try setting it as you have to around 1 bar and turn your temp control down. if it settles down adjust temp control up in small increments till you reach a happy setting. Same with hot water.

T.H.S, April 2007