Andrew - C asked ... Stannah 400?    |    Liam asked ... Belts for old WEBB Mower?    |    Leith asked ... Bosch Classix Type WKM41 front loader washing machine?    |    Pam asked ... Do I need to open the housing to dry the motor?    |    James asked ... Remove enterprise enrolment from an Asus Chromebook C523N?    |    Click here to ask your question

Is the Filling loop broken?

I have a Potterton Combi boiler, the pressure slowely rises even when just HW mode is selected. Is this a fault with the filling loop ( on of those you open using a screwdriver ) it is set at closed yet water is coming in. It rises when water isn't running even. Only way I can stop it is to keep mains tap turned off

Cheers
Liz, May 2007
best way to check is disconnect it. leave the end on connected to the mains water pipe and disconnected the other end then open your stopcock slowly and see if it passes water.

if still rises when disconnected its poss your dhw exchanger is passing water across to the primary circult.

hi-spec plumbing, May 2007