marc asked ... La machine 1 type 813?    |    Andrew - C asked ... Stannah 400?    |    Liam asked ... Belts for old WEBB Mower?    |    Leith asked ... Bosch Classix Type WKM41 front loader washing machine?    |    Pam asked ... Do I need to open the housing to dry the motor?    |    Click here to ask your question

baxi 100 e system boiler?

boiler reaches temp on stat pump runs on for a couple of minutes then stops will not fire back up unless i turn prog d/h/w of then back on cons no hot water
wwernham, July 2007
Sounds like the 2 or 3 way motorised diverter valve is sticking and allowing flow of water which the sensor inside the boiler needs to tell it to fire up. What you're doing when switching d/w/h to off then back on is to drive the motor (airing cupboard) from one side to the other allowing water flow. Hope this helps?

Chris, July 2007