Lou asked ... Mac Allister 35cm electric lawn mower?    |    Ronald Charlwood asked ... Beko fridge/freezer not cold enough?    |    John Broadbent asked ... Advise?    |    suzy asked ... Brother kh-940 not in sync with DAK9 in interactive knitting?    |    Susan asked ... How can I stop my steam iron spraying water with the steam?    |    Click here to ask your question

pressurising a SIME Super 90 boiler?

I have just switched on the boiler for the first time. I have bled one of the top two radiators until the air stopped coming through but the water has not spirted through yet and the other radiator needs to be bled too but there is no more air flowing. Have checked the boiler and the pressure is right down. Am I right to assume water needs to be let in to the system to get the pressure back up and allow me to bleed the last radiator? Having looked at the boiler I can't see how to do this?
Chris, September 2007
Thanks Brian.
Works perfectly now.

craig, October 2007
Am I right to assume water needs to be let in to the system to get the pressure back up and allow me to bleed the last radiator?

Yes!

look under boiler at pipework, find cold inlet and look for a tap with a flexible hose.

Use tap/s to pressurize to 1.5 bar, recheck after bleeding air from rads.

brian, October 2007