Liam asked ... Belts for old WEBB Mower?    |    Leith asked ... Bosch Classix Type WKM41 front loader washing machine?    |    Pam asked ... Do I need to open the housing to dry the motor?    |    James asked ... Remove enterprise enrolment from an Asus Chromebook C523N?    |    tom schwartz asked ... Bosch maxx 6?    |    Click here to ask your question

Valiant Combi Compact Boiler Nightmare?

Hello, can anyone help me please? It's looking like I'm going to have to call out a plumber and I cant afford it before Xmas. Basically, the pressure is low on reading & I need to know how to get the pressure up to one bar, there is no hot water or heating, I can hear the ignitor trying to light flame but not working. How do I top up water and obtain pressure in the system? Thank you thank you thank you.
Jennifer Allen, December 2005
you what you need to do is to turn the loop tap on . wich is located under the boiler.

ray, November 2006
Correct answer but the repair is not gas related therefore the engineer does not have to be Corgi Registered.

Heating Engineer, March 2006
Hi
As you give little details of boiler make i asume that the boiler you have has an external filling loop.
Where the pipes for your boiler go into the boiler you will see a flexipipe with an isolation valve like the one on your washing machine.this flexable pipe will screw on to a long brass valve close by called a non return valve.
Once this has been screwed on to this fitting you can turn on the isolation valve to re presurise the heating system.
Pressurise the system until it is just under 2 bar.
You will have to call a heating engineer out If the system looses preasure in a short time,if you do make sure you see his corgi reg card and make sure it is in date.

Andrew, December 2005