Andy asked ... How can I mend my MacAlistair 450w hedge trimmer?    |    Felix asked ... Hitachi vt-m70em?    |    Katie Bond asked ... Fixing auto threader on Baby Lock Enlighten Overlocker?    |    Chris. asked ... Miele W800 novotronic washing machine?    |    Larry asked ... How to stop my steam iron from leaking. Model dw2463 Rowenta?    |    Click here to ask your question

Baxi 105 e looses pressure?

I have to repressure my Baxi 105e everyday. The pressure falls from 2 to 0.5 bar in 24 hours. Where do I look for the leak?

If I don't do anything the boiler fails to fire

Any ideas?
Stan Balmer, January 2010
look at the (prv) this is the pressure relief valve that vents water outside when excessive pressure is reached inside boiler usually around the 3 bar mark.
with NO pressure in the boiler see (what air pressure is in the expansion vessel) (tyre pressure gauge needed) may be a big fat ZERO
Note
(if water comes OUT when the valve is depressed the internal diaphram has gone, a replacement expansion vessel will be needed)
if NO WATER comes out of the valve(good sign )just RE INFLATE using a car pump back up to 1 bar pressure.
now repressurise the central heating on the water side via the filler loop to about 1.2 to 1.5 bar COLD

wirecutterman, January 2010